CTECHI 220 V LiFePO₄ UPS (1–3 kVA) – Tower & 2U Rack-Mount, Online Double-Conversion Battery Backup
Detailed Product Features
Related Parameters
|
Tower Model |
Li HV C1K |
Li HV C1KS |
Li HV C2K |
Li HV C2KS |
Li HV C3K |
Li HV C3KS |
||||||||
|
Rack Model |
Li HV R1K |
Li HV R1KS |
Li HV R2K |
Li HV R2KS |
Li HV R3K |
Li HV R3KS |
||||||||
|
Capacity |
1KVA/900W |
2KVA/1.8KW |
3KVA/2.7KW |
|||||||||||
|
AC INPUT |
|
|||||||||||||
|
Wiring |
L/N+PE |
|||||||||||||
|
Rated Voltage |
208/220/230/240VAC |
|||||||||||||
|
Voltage Range |
90~300VAC |
|||||||||||||
|
Frequency Range |
40Hz~70Hz |
|||||||||||||
|
Input Power Factor |
≥0.99 |
|||||||||||||
|
AC OUTPUT |
|
|||||||||||||
|
Wiring |
L/N+PE |
|||||||||||||
|
Output Voltage |
208/220/230/240VAC |
|||||||||||||
|
Voltage Regulation |
±1% |
|||||||||||||
|
Output Frequency |
50/60±4Hz(Sync mode) ; 50/60Hz±0.1%(Free run) |
|||||||||||||
|
Waveform |
Pure sine wave |
|||||||||||||
|
Distortion(THDV%) |
<2%(Linear load); <7%(Non-Linear load) |
|||||||||||||
|
Overload Capability |
100%~105% continuous;60Sec.@105%~130% rated load;10Sec.@130%~150% rated load;0.3Sec.@>150% rated load. |
|||||||||||||
|
EFFICIENCY |
|
|||||||||||||
|
Line Mode |
88% |
89% |
90% |
|||||||||||
|
Battery Mode |
86% |
87% |
88% |
|||||||||||
|
BATTERY & CHARGER |
|
|||||||||||||
|
Rated Battery Voltage |
48VDC (default for 15cell of LiFePO4 ) |
|||||||||||||
|
Battery Capacity |
600WH |
External battery depends |
1000WH |
External battery depends |
1000WH |
External battery depends |
||||||||
|
Backup Time |
>40mins @ half load |
>30mins @ half load |
>20mins @ half load |
|||||||||||
|
Charging Current |
4A/8A |
|||||||||||||
|
Charging Voltage |
52.8V(default for 15cell of LiFePO4 ) / Customized according to battery request |
|||||||||||||
|
Charger Behavior & Protection |
CC. CV. floating. turn-off 4 states 3 over voltage protection loop, preserve interface for over temperature/over pressure switch off interface |
|||||||||||||
|
HMI |
|
|||||||||||||
|
LED Display |
Mains / battery status, load level, battery level, operation mode |
|||||||||||||
|
LCD Display with LED Indicator |
Input mains voltage, frequency, load level, operation mode, health status |
|||||||||||||
|
Standards Communication Interface |
(1) RS232 port (2) Network card: support SNMP,TCP/IP protocol , for remote monitor the UPS via smart phone APP, web page, PC monitor software, support server / NAS shutdown (3) Dry contact interface for BMS control (4) MODBUS For BMS interface |
|||||||||||||
|
ENVIRONMENT |
|
|||||||||||||
|
Temperature Range |
-10~50°C |
|||||||||||||
|
Relative Humidity |
0-98%(Non-condensing) |
|||||||||||||
|
Acoustics Noise |
<55dB @ 1 meters |
|||||||||||||
|
PHYSICAL |
|
|||||||||||||
|
Tower Dimension WxDxH (mm) |
C1K: 190x378x318 |
C2K: 190x427x318 |
C3K: 190x427x318 |
|||||||||||
|
C1KS: 145x397x220 |
C2KS: 145x397x220 |
C3KS: 190x378x318 |
||||||||||||
|
Rack Dimension WxDxH(mm) |
R1K: 440x400x88 (2U) |
R2K: 440x500x88 (2U) |
R3K: 440x650x88 (2U) |
|||||||||||
|
R1KS: 440x400x88 (2U) |
R2KS: 440x400x88 (2U) |
R3KS: 440x400x88 (2U) |
||||||||||||
|
Tower N.W (kg) |
10.8 |
5 |
16.5 |
5.5 |
18 |
7.9 |
||||||||
|
Rack N.W (kg) |
12.5 |
6.5 |
21.6 |
6.8 |
24.5 |
8.2 |
||||||||